Inductive or Transformer Load

Transformers are normally used to provide galvanic isolation between the primary & secondary, or to change the main supply voltage to the nominal load supply voltage i.e. 400V to 60V.

The thyristor power controller can switch either the primary or the secondary of the transformer but will need two completely different ways to control the load. When switching the primary of the transformer attention must be made to the high in-rush current on start-up, which can be 20 times the nominal current and will damage the fuses and/or thyristor semiconductors if not cared for.

Transformers are normally used to step the voltage down to a load. Voltage is typically stepped down because the resistance of an element is limited and the load requires high current with low voltage. Another advantage to stepping down the voltage is that current is increased proportionally. Therefore, the SCR can switch relatively low current on the primary side of the transformer while the current delivered to the load is quite high.Because a transformer is inductive, phase angle firing is used on transformer coupled loads regardless of the element characteristics.

A thyristor controller with phase angle firing, soft-start and current limit is typically employed, or if the load is a fixed resistance then delayed triggering + burst firing can be considered.

The effect of current limit with an inductive load
Fig. 1 - The effect of Current Limit
Switching the primary of a transformer
Fig. 2 - Switching the Transformer Primary Winding

Switching the secondary of the transformer is the same as driving a standard resistive load. The issue with this solution is the size of thyristor unit can be 8 times larger than a unit to switch the primary (i.e. 25A v 200A).

Switching the secondary of a transformer
Fig. 3 - Switching the Transformer Secondary Winding

So to summarise:

Switching primary of transformer coupled with fixed/variable resistance load?

  •  Use a Thyristor with phase angle + soft-start + current limit

Switching primary of transformer coupled with fixed resistance load?

  • Consider a Thyristor with delayed triggering + burst firing

Switching secondary of transformer coupled with fixed/variable resistance load?

  • Use a Thyristor with the same standard considerations as fixed/variable resistance loads

 

Product Suggestion:
For switching the primary of a single phase transformer we suggest REVEX 1PH for currents up to 210A, or REVO-C 1PH.
For 3 phase transformer loads we recommend REVO-C 3PH.

Our Address
Unit 9 Harvington Business Park, Brampton Rd, Eastbourne, BN22 9BN, UK
Need Help?
We aim to reply to email enquiries within 20 minutes (during normal working hours).
Logo CDA_R_Bianco
Opening Hours
CD Automation UK Limited © Copyright 2026. All Rights Reserved.

🎉 Thank you! Your download is ready.

You can access your PDF now by clicking the link below:
Inside, you’ll discover the 5 common mistakes that can affect machine performance and how to avoid them to save time, reduce downtime, and improve product quality.