Power Controller - REVO-C 1PH-480V-30A

£1.00
Part Number:
REVO-C 1PH 480V-30A

REVO-C (RC1030-4) single phase (1PH) solid state relay / thyristor (SCR) power controller, suitable for loads up to 480Vac and a maximum current rating of 30 amps.

A wealth of options include Wi-Fi, Datalogging, Energy Totalising, Current Limit and Heater Break Alarm as well as industry standard communications options such as Modbus, Profibus & Profinet, enabling equipment and factory automation.

Firing Range
Zero Cross (ZC), Half Cycle (HC), Single Cycle (SC), Burst Firing (BF), Delayed Triggering (DT), Phase Angle (PA), Soft Start (SS)
Communication
Modbus RTU as standard, Profibus DP and Profinet as option.
Option
Current Limit, Heater Break Alarm, WiFi, Datalogging, Energy Totalizer.
Ideal For
All load types

pointer Check out our Video Tutorials

112

112

Never feel alone again with REVO-CONNECT

112

Revo Connect App

112

A breakthrough in the field of power control, CD Automation now gives you functionality that will take the pressure off if things are not going to plan.

Traditionally power controllers are hidden in the control cabinet and once powered, almost impossible to monitor once the cabinet door is closed.

If your process is not behaving, it’s not easy to see what’s wrong.

112
Revo Connect App

112

Now with the FREE CD Automation Smartphone APP you can locally review settings and monitor alarms with the door closed.

If you need expert advice, upload critical data within minutes and feel the protection of our remote support from anywhere in the world.

Revo Connect App

112

CD Automation’s REVO-C is an intelligent family of power controllers that delivers breakthrough thermal performance, extended heater life and now with smartphone connectivity.

Watch our latest video above and see how easy and simple to use the REVO-CONNECT truly is!

112

112

CD Automation's new REVO-C thyristor (SCR) power controller range is flexible and powerful, and available with a variety of options allowing one platform to be re-used across a wide range of applications saving time and money. REVO-C single phase models include sizes from 35 to 800 amps, with 3 voltage ranges up to 480Vac, 600Vac and 690Vac.

A wealth of options include Wi-Fi, Datalogging, Energy Totalising, Current Limit and Heater Break Alarm as well as industry standard communications options such as Modbus, Profibus & Profinet, enabling equipment and factory automation.

Controller firing modes include zero cross, burst firing, single cycle and half cycle, delayed triggering and phase angle. These smart algorithms enable the product to easily control a wide base of heater loads including Nichrome®, moly, silicon carbide, tungsten quartz and infrared lamps and transformer-coupled loads. REVO-C 1PH offers a comprehensive list of modular options that deliver space and labour savings including controlled legs (1, 2 or 3), semiconductor fusing, load current measurement and user interface.

Call today for a quick quote or use our free configuration tool to select the correct thyristor regulator for your application.
Do you need a 3 phase unit? Click here for 4 wire loads (or if you are unsure), or here for 3 wire loads

 

REVO-C equals REVO-Connect with its unique mobile phone app giving you access to the power controller from outside the cabinet. Extremely helpful if you have questions with your process control and want to view key parameter values with the process live and the control cabinet closed.

More Information
Product Name Power Controller - REVO-C 1PH-480V-30A
Software

Thyristor Configurator

Thyristor Configurator Software. Version V5.7.0.2. 23.7MB download file size.

Firing Range Zero Cross (ZC), Half Cycle (HC), Single Cycle (SC), Burst Firing (BF), Delayed Triggering (DT), Phase Angle (PA), Soft Start (SS)
Input Signal

DC logic (SSR), 0-20mA, 4-20mA, 0-10Vdc, 10K Pot

Communication Modbus RTU as standard, Profibus DP and Profinet as option.
Feedback Type Voltage (V), Current (I) and Power (VxI), or Voltage Square (V2) and Current Square (I2) with additional transfer to VxI
Option Current Limit, Heater Break Alarm, WiFi, Datalogging, Energy Totalizer.
Ideal For All load types
Approvals cUL and CE + EMC approved
Altitude Over 1000m of altitude reduce the nominal current of 2% for each 100m.
Auxiliary Voltage Supply

90:130Vac 8VA Max
170:265Vac 8VA Max (Standard with phase to neutral)
230:345Vac 8VA Max
300:530Vac 8VA Max (Standard with phase to phase)
510:690Vac 8VA Max

Controlled Phases 1
Heater Break Alarm To diagnose partial or total load failure with automatic setup, relay alarm output and LED indication, available as an option
Humidity From 5 to 95% but without condensation or surface ice
Mounting DIN-Rail or Screw mounting
Load Type Single Phase (Phase to Phase or Phase to Neutral)
Panel Sealing IP20
Storage Temperature -25 °C to 50 °C Max
Voltage Power Supply From 24V to 480Vac (Standard) or 600V & 690V as option on specific models
Voltage Frequency Automatically from 47 to 70 Hz

111

CD Automation Cares

Every thyristor power controller product sold at CD Automation benefits our local and global environment. We believe the more you give in life, the more you will receive so we are eternally grateful to be able to pay-it-forward and share our platform to help causes that matter to all of us.

giving

discover

111

111

111