Thyristor Power Controller - REVO-CL 1PH

£1.00
Part Number:
REVO-CL 1PH

Designed to drive single phase transformer, resistive and inductive loads up to 700A. RCL includes current limit and voltage, current & power feedback. Now superseded by REVO-C 1PH.

Firing Range
Phase Angle, Delayed Triggering + Burst Firing, Soft Start + Phase Angle
Communication
RS485 Modbus as standard, Profibus DP, Profinet, Ethernet IP as option
Option
Current Limit as standard, Heater Break Alarm as option
Ideal For
Switching primary of single phase transformer

Designed specifically to drive inductive & transformer single phase loads, REVO-CL thyristor power controller provides the user with optimum control of the process and ease of set-up & maintenance.

The Front panel keypad & display allows total flexibility for the user with full configuration of the process & digital input types and firing & control modes, to suit the application. Real time values such as the Voltage, Current & Power can be read from the display. Internal quick-blow semiconductor fuses as standard provide complete protection for the phase angle thyristor.

Additional features such as current limit, profiling and RS485 comms comes as standard. Heater break alarm available as an option.

More Information
Product Name Thyristor Power Controller - REVO-CL 1PH
Current Range All Others 35A, 40A, 60A, 90A, 120A, 150A, 180A, 210A, 280A, 400A, 500A, 600A, 700A
Software No
Firing Range Phase Angle, Delayed Triggering + Burst Firing, Soft Start + Phase Angle
Input Signal

0-10V, 4-20mA, 0-10Vdc, RS485 Comms

Communication RS485 Modbus as standard, Profibus DP, Profinet, Ethernet IP as option
Feedback Type Voltage (V), Power (VxI), Voltage Square (V2), Current, (I)
Option Current Limit as standard, Heater Break Alarm as option
Ideal For Switching primary of single phase transformer
Approvals Complies with CE specification
Altitude Over 1000 m of altitude reduce the nominal current of 2% for each 100m
Auxiliary Voltage Supply

90:130Vac 8VA Max
170:265Vac 8VA Max (Standard with phase to neutral)
230:345Vac 8VA Max
300:530Vac 8VA Max (Standard with phase to phase)
510:690Vac 8VA Max 
600:760Vac 8VA Max

Controlled Phases 1
Heater Break Alarm Heater Break Alarm to diagnose partial or total load failure with automatic setup, relay alarm output and front LED indication. Available as an option
Humidity From 5 to 95% without condensation or ice conditions
Mounting DIN RAIL Mounting or Panel Mounting
Load Type Inductive & Transformer requiring Current Limit
Panel Sealing Please ask
Storage Temperature -25 °C to 70 °C Max
Voltage Power Supply From 24V to 480Vac Max (Std) or 600Vac option available on all sizes. 690Vac available from 280A to 700A as option.
Voltage Frequency Automatically from 47 to 70 Hz

111

CD Automation Cares

Every thyristor power controller product sold at CD Automation benefits our local and global environment. We believe the more you give in life, the more you will receive so we are eternally grateful to be able to pay-it-forward and share our platform to help causes that matter to all of us.

giving