Thyristor Power Controller - REVO-M 1PH

£1.00
Part Number:
REVO-M 1PH

Universal thyristor (SCR) power controller (RM1) with RS485 comms and front panel display as standard. Now superseded by REVO-C 1PH.

REVO-M provides the user total flexibility with the ability to select any input, firing & feedback type. Either via the front panel display & keypad, or via the RS485 comms port the user has opportunity to change or view any parameter

Firing Range
Zero Cross (ZC), Burst Firing (BF), Single Cycle (SC), Phase Angle (PA), Soft Start (SS), Delayed Triggering (DT)
Communication
RS485 Modbus as standard, Profibus DP, Profinet, Ethernet IP as option
Option
Heater Break Alarm
Ideal For
Normal Resistance, Short, Medium & Long Wave IR, and Silicon Carbide load types

REVO-M SCR from CD Automation is a single phase burst fire power controller & phase control thyristor ideal for normal & variable resistive type loads.

Selection is made either via the front panel display & keypad, or via the RS485 comms port and/or configuration software.

The operator has the opportunity to change or view any parameter in the thyristor, as well as monitoring process values such as the Voltage, Current & Power.

Choice of inputs from DC Logic (Solid state relay), 4-20mA, 0-10Vdc and RS485 comms and firing types such as Burst Firing (for Burst fire power controller), Single Cycle & Phase Angle firing (Phase control thyristors) as standard. Internal quick-blow semiconductor fuses provide complete protection for the thyristor power regulator. Heater break alarm available as an option.

More Information
Product NameThyristor Power Controller - REVO-M 1PH
Current Range All Others35A, 40A, 60A, 90A, 120A, 150A, 180A, 210A, 300A, 400A, 500A, 600A, 700A
Software

Thyristor Configurator

Thyristor Configurator Software. Version V5.7.0.2. 23.7MB download file size.

Firing RangeZero Cross (ZC), Burst Firing (BF), Single Cycle (SC), Phase Angle (PA), Soft Start (SS), Delayed Triggering (DT)
Input Signal

DC logic (SSR), 4-20mA, 0-10Vdc, 10K Pot, RS485 Comms

CommunicationRS485 Modbus as standard, Profibus DP, Profinet, Ethernet IP as option
Feedback TypeVoltage (V), Power (VxI)
OptionHeater Break Alarm
Ideal ForNormal Resistance, Short, Medium & Long Wave IR, and Silicon Carbide load types
ApprovalsCE + EMC approved
AltitudeOver 1000m of altitude reduce the nominal current of 2% for each 100m
Auxiliary Voltage Supply

90:130Vac 8VA Max
170:265Vac 8VA Max (Standard with phase to neutral)
230:345Vac 8VA Max
300:530Vac 8VA Max (Standard with phase to phase)
510:690Vac 8VA Max

Controlled Phases1
Heater Break AlarmTo diagnose partial or total load failure with automatic setup, relay alarm output and LED indication, available as an option
HumidityFrom 5 to 95% but without condensation or the effects of ice
MountingDIN-Rail or Screw mounting
Load TypeSingle Phase (Phase to Phase, or Phase to Neutral)
Panel SealingIP20
Storage Temperature -25 °C to 50 °C Max
Voltage Power SupplyFrom 24V to 480V (Std) or 600V & 690V as option on specific models
Voltage FrequencyAutomatically from 47 to 70 Hz