Solid State Relay - REVO-S 2PH 480V-150A

£1.00
Part Number:
REVO-S 2PH 480V-150A

Compact & low cost, the New REVO-S 2 Phase solid state relay / thyristor power controller is designed to replace contactors and is suitable for all resistive switching applications.

REVO-S 2PH is a self-contained unit mounted on CD Automation designed heat-sinks, optimised for maximum heat dissipation. Integral quick-blow fuse & holder can be supplied on unit sizes 30A to 40A units as an option, with internal fixed fuses on 60A upwards as standard.

The REVO-S thyristor unit also has the option of 4-20mA or 0-10Vdc linear input with Burst Firing set for 4, 8 or 16 cycles. Heater break alarm available as an option.

Firing Range
Zero Cross (SC), Burst Firing (BF)
Communication
None
Option
Heater Break Alarm
Ideal For
Normal Resistance, Medium & Long Wave Infrared load types
  • Thyristor suitable for resistive, medium or long wave infrared and heater battery loads
  • Current range - 30A, 35A, 40A, 60A, 90A, 120A, 150A, 180A, 210A, 280A, 400A, 450A, 500A, 600A, 700A
  • Supply voltage up to 480V or 600V AC as option
  • Fully isolated from the power
  • Zero crossing firing mode (ZC) or Burst Firing (4, 8 or 16 cycles selectable)
  • Logic input signal 4 to 30V DC typical (SSR) plus 4-20mA or 0-10V DC Linear input as an option
  • Constant current drain, independent of supply voltage with SSR input
  • Heater Break (HB) alarm to diagnose partial or total load failure with automatic setting, relay alarm output and front LED indication. Available as an option
  • Side by side mounting
  • Special design Heatsink with high dissipation value
  • IP20 protection
  • Complies with CE and cUL specification
  • Can be used in conjunction with REVO-PC to provide multi-zone control
More Information
Product Name Solid State Relay - REVO-S 2PH 480V-150A
Firing Range Zero Cross (SC), Burst Firing (BF)
Input Signal

DC logic (SSR), 4-20mA, 0-10Vdc

Communication None
Feedback Type Open loop
Option Heater Break Alarm
Ideal For Normal Resistance, Medium & Long Wave Infrared load types
Approvals cUL and CE + EMC approved
Altitude Over 1000m of altitude reduce the nominal current of 2% for each 100m.
Auxiliary Voltage Supply

12:24Vac/dc (30A to 210A only with DC Linear input or HBA), otherwise available as follows:

90:130Vac 8VA Max
170:265Vac 8VA Max (Standard)
230:345Vac 8VA Max
300:530Vac 8VA Max (Standard)
510:690Vac 8VA Max

Controlled Phases 2
Heater Break Alarm To diagnose partial or total load failure with automatic setup, relay alarm output and LED indication, available as an option
Humidity From 5 to 95% but without condensation or surface ice
Mounting Screw mounting
Load Type Normal Resistance, MWIR, LWIR, Heater Battery
Panel Sealing IP20
Storage Temperature -25 °C to 50 °C Max
Voltage Power Supply 24V minimum to 480V, 600V On request
Voltage Frequency Automatically from 47 to 70 Hz

CD Automation Cares

Every product sold at CD Automation benefits our local and global environment. We believe the more you give in life, the more you will receive. Each one of us are grateful to be able to pay-it-forward and share our platform to help causes bigger than all of us.

giving

discover