Thyristor Power Controller - REVO-M 2PH

£1.00
Part Number:
REVO-M 2PH

Universal power controller designed to drive 3 phase resistive loads configured as delta or star connection without neutral (3 wire). Now superseded with REVO-C 2PH.

Firing Range
Zero Cross (ZC), Burst Firing (BF)
Communication
RS485 Modbus as standard, Profibus DP, Profinet, Ethernet IP as option
Option
Heater Break Alarm
Ideal For
Normal Resistance, Medium & Long Wave IR, and Silicon Carbide load types

The fully universal REVO M 2 phase thyristor power controller provides the user total flexibility with the ability to select any input, firing & feedback type.

Either via the front panel display & keypad, or via the RS485 comms port the user has opportunity to change or view any parameter, including to read & display process values such as the Voltage, Current & Power.

Choice of inputs from DC Logic (SSR), 4-20mA, 0-10Vdc, 10K Potentiometer & RS485 comms and firing types such as Zero Cross Firing & Burst Firing as standard. Internal quick-blow fuses provide complete protection for the thyristor. Heater break alarm available as an option.

More Information
Product Name Thyristor Power Controller - REVO-M 2PH
Current Range All Others 30A, 35A, 40A, 60A, 90A, 120A, 150A, 180A, 210A, 280A, 400A, 450A, 500A, 600A, 700A
Software

Thyristor Configurator

Thyristor Configurator Software. Version V5.7.0.2. 23.7MB download file size.

Firing Range Zero Cross (ZC), Burst Firing (BF)
Input Signal

DC logic (SSR), 4-20mA, 0-10Vdc, 10K Pot, RS485 Comms

Communication RS485 Modbus as standard, Profibus DP, Profinet, Ethernet IP as option
Feedback Type Voltage (V), Power (VxI)
Option Heater Break Alarm
Ideal For Normal Resistance, Medium & Long Wave IR, and Silicon Carbide load types
Approvals CE + EMC approved
Altitude Over 1000m of altitude reduce the nominal current of 2% for each 100m
Auxiliary Voltage Supply

90:130Vac 8VA Max
170:265Vac 8VA Max (Standard with phase to neutral)
230:345Vac 8VA Max
300:530Vac 8VA Max (Standard with phase to phase)
510:690Vac 8VA Max

Controlled Phases 2
Heater Break Alarm To diagnose partial or total load failure with automatic setup, relay alarm output and LED indication, available as an option
Humidity From 5 to 95% but without condensation or the effects of ice
Mounting DIN-Rail or Screw mounting
Load Type 3 Phase (3 wire)
Panel Sealing IP20
Storage Temperature -25 °C to 50 °C Max
Voltage Power Supply From 24V to 480V (Std) or 600V & 690V as option on specific models
Voltage Frequency Automatically from 47 to 70 Hz